iGrid T&D

iGrid T&D iRTU Remote Terminal Unit

Internal I/O cards up to 48 DI, 16 relay DO and 16 AI (±20 mA, 0.15%) · IEC 61850 MMS/GOOSE, IEC 60870-5-101/102/103/104, DNP3.0, Modbus RTU/TCP, DLMS, Profibus DP

Overview

A modular RTU built for substations that combines data acquisition, built-in I/O, protocol conversion and gateway duties in one DIN-rail unit. Utilities and integrators use it as a substation RTU, bay controller, feeder RTU or PV plant gateway.

  • Collects data from old and new IEDs and reports to several control centres at once
  • Converts between protocols such as Modbus to IEC 61850 and IEC 101 to IEC 104
  • Built-in IEC 61131-3 PLC with LD, FBD, ST and SFC programming
  • Time sync via PTP/IEEE 1588 and NTP with 1 µs timestamp resolution
  • Configured with the iConf tool; internal web server for live monitoring

Models: iRTU B0 Series (e.g. iRTU-B0C1), iRTU S0, iRTU S3, iRTU M0, iRTU M1, iRTU M2.

Specifications

I/OInternal I/O cards up to 48 DI, 16 relay DO and 16 AI (±20 mA, 0.15%)
MountingIP30 enclosure, DIN rail, 173 x 78.4 x 137 mm; -25 to +70 °C
ProtocolsIEC 61850 MMS/GOOSE, IEC 60870-5-101/102/103/104, DNP3.0, Modbus RTU/TCP, DLMS, Profibus DP
Ports & CPUUp to 4 serial + 4 Ethernet (2 FX100 fibre, PRP/HSR/RSTP); optional 4G/3G/GPRS modem; ARM Cortex-A7 @ 528 MHz
BrandiGrid T&D

Datasheet available on request.